Identify motor data

Identify motor data
Danger to life from machine movements while motor data identification is in progress
The stationary measurement can turn the motor a number of revolutions. The rotating
measurement accelerates the motor up to the rated speed. Secure dangerous machine parts
before starting motor data identification:
● Before switching on, ensure that nobody is working on the machine or located within its
● Secure the machine's working area against unintended access.
● Lower suspended loads to the floor.
Preconditions
● You selected a method of motor data identification during quick commissioning, e.g.
measurement of the motor data while the motor is stationary.
When quick commissioning is complete, the inverter issues alarm A07991.
● The motor has cooled down to the ambient temperature.
An excessively high motor temperature distorts the results of motor data identification.
● The PC and inverter are connected to each other online.
Procedure with STARTER
To initiate motor data identification and optimize the motor control, proceed as follows:
1. Open the control panel.
Figure 5-18
2. Assume master control for the inverter.
3. Set the "Enable signals"
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
WARNING
working area.
Control panel
Commissioning
5.5 Quick commissioning with a PC