Advanced commissioning
6.3 Adapt the default setting of the terminal strip
Dead band
With the control enabled, electromagnetic interference on the signal cable can cause the motor
to slowly rotate in one direction in spite of a speed setpoint = 0.
p0764[0]
p0764[1]
Using an analog input as digital input
An analog input can also be used as digital input.
186
Analog inputs dead zone, AI 0 (factory setting: 0)
Analog inputs dead zone, AI 1 (factory setting: 0)
Digital inputs (Page 179)
The dead band acts on the zero crossover of
the analog input characteristic. Internally, the
inverter sets its speed setpoint = 0, even if
the signal at the analog input terminals is
slightly positive or negative. This prevents
the inverter from rotating the motor at a
speed setpoint = 0.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD