Technical data
10.6 Technical data, PM230 Power Module
10.6.2

General technical data, PM230

Property
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Line impedance
Inrush current
Pulse frequency (factory set‐
ting)
Electromagnetic compatibility
Braking methods
Degree of protection
Operating temperature at
Storage temperature
Relative humidity
Pollution
Environmental requirements
Shock and vibration
Installation altitude
Permissible short-circuit cur‐
rent
Overvoltage category
Standards
If fuse-protected with a listed Class J or 3NE1 fuse, rated voltage 600 VAC with the rated current of the specific inverter.
1)
UL available soon for frame sizes D ... F
2)
460
Version
3-phase 380 ... 480 VAC ± 10%
3-phase 0 VAC ... input voltage x 0.95 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 Hz ... 550 Hz, depending on the control mode
0.9
Uk ≤ 1%, line reactor not permissible
< LO base load input current
4 kHz
The pulse frequency can be increased in 2 kHz steps up to 16 kHz (up to 8 kHz for 55 kW
and 75 kW). An increase in the pulse frequency results in a lower output current.
Devices with filters in compliance with EN 61800-3: 2004 are suitable for Category C2 en‐
vironments.
DC braking
IP20 built-in units
IP20 when mounted in a control cabinet
PT devices
IP54 on the control cabinet wall
LO base load power without derating
HO base load power without derating
LO/HO base load power with derating:
Restrictions for special ambient conditions (Page 474)
-40° C ... +70° C
< 95% - condensation not permissible
Protected according to pollution degree 2 according to EN 61800-5-1: 2007
Protected against damaging chemical substances according to environmental class 3C2
according to EN 60721-3-3: 1995
● Long-term storage in the transport packaging according to Class 1M2 according to
EN 60721‑3‑1: 1997
● Transport in the transport packaging according to Class 2M3 according to EN 60721-3-2:
1997
● Vibration during operation according to Class 3M2 according to EN 60721-3-3: 1995
without derating:
up to 1000 m above
with derating:
sea level
up to 4000 m above
sea level
Frame size D ... F: 65 kA
Supply circuits:
Non-supply circuits:
UL
, CE, C-tick
1),2)
The drive only satisfies the UL requirements when UL-certified fuses are used.
Restrictions for special ambient condi‐
tions (Page 474)
1)
Overvoltage category III
Overvoltage category II
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
0° C ... +40° C
0° C ... +50° C
Up to 60° C