General Technical Data, 400 V Inverters - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.5.2

General technical data, 400 V inverters

Property
Line voltage
Line system configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category ac‐
cording to EN 61800-5-1
Pulse frequency
Short-circuit current rating
(SCCR) and branch protec‐
tion
Braking methods
Degree of protection ac‐
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection according
to EN 50274
Cooling in compliance with
EN 60146
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Version
3 AC 380 V ... 480 V ± 10% (in operation -20% < 1 min)
Grounded TN/TT line systems or non-grounded IT line systems
Uk < 4%, line reactor is not required
> 0.9
3 AC 0 V ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
Factory setting
● 4 kHz for devices with an LO base load power < 75 kW
● 2 kHz for devices with an LO base load power ≥ 75 kW
Can be adjusted in 2 kHz steps as follows:
● 2 kHz ... 16 kHz for devices with an LO base load power < 55 kW
● 2 kHz ... 8 kHz for devices with an LO base load power ≥ 55 kW
● 2 kHz ... 4 kHz for devices with an LO base load power ≥ 110 kW
If you increase the pulse frequency, the inverter reduces the maximum output current.
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
support.industry.siemens.com/cs/ww/en/view/109479152)
DC braking, compound braking
IP20
Must be installed in a control cabinet
The inverters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
10.5 Technical Data, PM240P-2 Power Module
Technical data
(https://
449