Advertisement

Saving the settings and series commissioning
7.2 Saving the settings to a PC
5. Enter the password for the safety functions.
If the password is the factory default, you are prompted to change the password.
If you try to set a password that is not permissible, the old password will not be changed.
6. Click the "End safety commissioning" button.
7. Confirm the prompt for saving your settings (copy RAM to ROM).
8. Disconnect the online connection.
9. Switch off the inverter supply voltage.
10.Wait until all LEDs on the inverter go dark (no voltage condition).
11.Switch on the inverter supply voltage again.
You have transferred the settings from the PG to the inverter with Startdrive and have activated
the safety functions.
360
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD