Advanced commissioning
6.27 Automatic restart
Advanced settings
If you with to suppress the automatic restart function for certain faults, then you must enter the
appropriate fault numbers in p1206[0 ... 9].
Example: p1206[0] = 07331 ⇒ No restart for fault F07331.
Suppressing the automatic restart only functions for the setting p1210 = 6, 16 or 26.
Danger to life if an OFF command has no effect.
When the inverter is only controlled via the fieldbus interface, the motor restarts with the
setting p1210 = 6, 16, 26 – even if the communication link is currently interrupted. When
communication is interrupted, the control system cannot switch off the motor.
● Enter the fault number of the communication error in parameter p1206.
338
WARNING
Example:
Fault number F01910 means: Communication via PROFIBUS failed.
Set p1206[n] = 1910 (n = 0 ... 9).
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD