Siemens SINAMICS G120 Operating Instructions Manual page 495

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Parameter
p20033 = 440
p20159 = 5000.00
p20158 = 722.0
p20030[0] = 20160
p20030[1] = 722.1
p0840 = 20031
Explanation of the example using the ON/OFF1 command
Parameter p0840[0] is the input of the "ON/OFF1" block of the inverter. Parameter r20031 is
the output of the AND block. To interconnect ON/OFF1 with the output of the AND block, set
p0840 = 20031.
p20030[0...3]
Figure A-8
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Description
Run sequence of the AND logic block within runtime group 5 (processing
after the time block)
Setting the delay time [ms] of the time module: 5 seconds
Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
Interconnect the timer block to the 1st input of the AND
Interconnect the status of DI 1 with the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
Interconnect the AND output to ON/OFF1
p0840[0] = 20031
p0840[0]
&
r20031
20031
AND 0
Interconnecting blocks by setting p0840[0] = 20031
A.4 Interconnecting signals in the inverter
ON/OF
F1
Appendix
495