Installing
4.1 EMC-compliant setup of the machine or plant
4.1.3

Electromechanical components

Radio interference suppression
● Connect interference suppression elements to the following components:
– Coils of contactors
– Relays
– Solenoid valves
– Motor holding brakes
● Connect the interference suppression element directly at the coil.
● Use RC elements or varistors for AC-operated coils and freewheeling diodes or varistors
for DC-operated coils.