Technical data, CU240E-2 Control Unit

Feature
Fieldbus interface
Operating voltage
Current consumption
Power loss
Output voltages
Setpoint resolution
Digital inputs
Pulse input
Analog inputs
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Data
CU240E‑2, CU240E‑2 F
CU240E‑2 DP,
CU240E‑2 DP‑F
CU240E‑2 PN,
CU240E‑2 PN‑F
You have two options for the Control Unit power supply:
● Supply from the Power Module
● External supply via terminals 31 and 32 with 20.4 ... 28.8 VDC.
Use a power supply with protective extra low voltage (PELV according to EN 61800-5-1),
Class 2.
The 0 V of the power supply must be connected to the PE of the plant/system through a low-
ohmic connection.
The power supply is electrically isolated from the control terminals.
max 0.5 A
5.0 W
+24 V out (terminal 9),18 V ... 28.8 V, max. 100 mA
+10 V out (terminals 1 and 35), 9.5 V ... 10.5 V, max. 10 mA
0.01 Hz
6 (DI 0 ... DI 5)
1 (DI 3)
2 (AI 0, AI 1)
10.2 Technical data, CU240E-2 Control Unit
With RS485 interface for the fol‐
lowing protocols:
● USS
● Modbus RTU
With PROFIBUS interface
With PROFINET interface
Plus power loss of the output voltages.
● Low < 5 V, high > 11 V
● Electrically isolated
● 30 V maximum input voltage
● 5.5 mA current consumption
● SIMATIC-compatible
● PNP/NPN switchable
● 10 ms response time for debounce time p0724 = 0.
Maximum frequency 32 kHz
● Differential input
● 12-bit resolution
● 13 ms ± 1 ms response time
● AI 0 and AI 1 can be switched over:
0 V ... 10 V or ‑10 V ... +10 V (typical power consumption:
0.1 mA, voltage < 35 V)
0 mA ... 20 mA (120 Ω input resistance, voltage < 10 V,
current < 80 mA)
● If AI 0 and AI 1 are configured as supplementary digital inputs:
Voltage < 35 V, low < 1.6 V, high > 4.0 V, 13 ms ± 1 ms
response time for debounce time p0724 = 0.
Technical data
Article numbers:
Overview of Control
Units (Page 31)
421