Technical Data, Pm240-2 Power Module; High Overload - Low Overload Pm240-2 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.4

Technical data, PM240-2 Power Module

Protective organs for the Power Module
The fuses listed in the following tables are examples of suitable fuses.
Additional components for branch protection are available in the Internet:
Branch protection and short-circuit strength according to UL and IEC
support.industry.siemens.com/cs/ww/en/view/109479152)
10.4.1

High overload - low overload PM240-2

Typical inverter load cycles
Figure 10-1
Property
Ambient conditions for transport in the transport packaging
Climatic ambient conditions
Mechanical ambient condi‐
tions
Protection against chemical
substances
Biological ambient condi‐
tions
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions
Protection against chemical
substances
Biological ambient condi‐
tions
Ambient conditions in operation
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
"Low Overload" and "High Overload" load cycles
Version
‑ 40° C ... + 70° C, according to Class 2K4 to EN 60721‑3‑2
maximum humidity 95% at 40° C
● FSA ... FSC: Shock and vibration permissible according to 1M2 to EN 60721‑3‑2
● FSD ... FSF: Shock and vibration permissible according to 2M3 to EN 60721‑3‑2
Protected according to Class 2C2 to EN 60721‑3‑2
Suitable according to Class 2B1 to EN 60721‑3‑2
‑ 25° C ... + 55° C, according to Class 1K3 to EN 60721‑3‑1
Protected according to Class 1C2 to EN 60721‑3‑1
Suitable according to class 1B1 to EN 60721‑3‑1
10.4 Technical data, PM240-2 Power Module
(https://
Technical data
425