Table 10-3
PM240-2, IP20, Frame Size B, 1-ph./3-ph. AC 200 V ... 240 V
Article no. without filter
Article no. with filter
LO base load output
LO base load input current, 1-ph. AC
LO base load input current, 3-ph. AC
LO base load output current
HO base load output
HO base load input current, 1-ph. AC
HO base load input current, 3-ph. AC
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Table 10-4
PM240-2, PT, Frame Size B, 1-ph./3-ph. AC 200 V ... 240 V
Article no. without filter
Article no. with filter
LO base load output
LO base load input current, 1-ph. AC
LO base load input current, 3-ph. AC
LO base load output current
HO base load output
HO base load input current, 1-ph. AC
HO base load input current, 3-ph. AC
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.08 through the heatsink
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
6SL3210-1PB15-5UL0
6SL3210-1PB15-5AL0
1.1 kW
13.5 A
7.8 A
6 A
0.75 kW
11.8 A
5.5 A
4.2 A
3NA3812 (32 A)
35 A
0.05 kW
9.2 l/s
2.8 kg
3.1 kg
6SL3211-1PB21-0UL0
6SL3211-1PB21-0AL0
2.2 kW
24.0 A
13.6 A
10.4 A
1.5 kW
20.9 A
9.7 A
7.4 A
3NA3812 (32 A)
35 A
0.12 kW
1)
9.2 l/s
3.4 kg
3.7 kg
10.4 Technical data, PM240-2 Power Module
6SL3210-1PB17-4UL0
6SL3210-1PB17-4AL0
1.5 kW
18.1 A
9.7 A
7.4 A
1.1 kW
15.8 A
7.8 A
6 A
3NA3812 (32 A)
35 A
0.07 kW
9.2 l/s
2.8 kg
3.1 kg
Technical data
6SL3210-1PB21-0UL0
6SL3210-1PB21-0AL0
2.2 kW
24.0 A
13.6 A
10.4 A
1.5 kW
20.9 A
9.7 A
7.4 A
3NA3812 (32 A)
35 A
0.12 kW
9.2 l/s
2.8 kg
3.1 kg