Advanced commissioning
6.15 Setpoints
6.15.2
Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Figure 6-29
Table 6-33
Parameter
p1070 = 755[0]
p1075 = 755[0]
You must adapt the analog input to the connected signal, e.g. ± 10 V or 4 ... 20 mA.
252
Example: Analog input 0 as setpoint source
Setting with analog input 0 as setpoint source
Remark
Main setpoint
Interconnect the main setpoint with analog input 0
Additional setpoint
Interconnect the additional setpoint with analog input 0
Analog inputs (Page 183)
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD