Advanced commissioning

6.8 Drive control via Ethernet/IP

6.8
Drive control via Ethernet/IP
EtherNet/IP is an Ethernet-based fieldbus. EtherNet/IP is used to transfer cyclic process data
as well as acyclic parameter data.
Settings for Ethernet/IP
Parameter
p2030 = 10
p8920
p8921
p8922
p8923
p8924
p8925
p8980
p8982
Further information
Further information about USS is provided in the "Fieldbus" function manual.
218
Explanation
Fieldbus interface protocol selection: Ethernet/IP
PN Name of Station
PN IP address (Factory setting: 0)
PN default gateway (factory setting: 0)
PN Subnet Mask (Factory setting: 0)
PN DHCP mode (Factory set‐
ting: 0)
PN interface configuration
(Factory setting: 0)
Ethernet/IP profile (Factory setting: 0)
A change only becomes effective after the inverter power
supply has been switched off and switched on again.
Ethernet/IP ODVA speed scaling (Factory setting: 128)
A change only becomes effective after the inverter power supply has been switched off
and switched on again.
123: 32
124: 16
125: 8
126: 4
Overview of the manuals (Page 504)
0: DHCP off
2: DHCP on, identification based on MAC address
3: DHCP on, identification based on Name of Station
0: No function
1: Reserved
2: Save the configuration and activate
3: Delete configuration
127: 2
128: 1
129: 0.5
130: 0.25
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
0: SINAMICS
1: ODVA AC/DC
131: 0.125
132: 0.0625
133: 0.03125