Setting the forced checking procedure (test stop)

Requirement
You are online with STARTER or Startdrive online.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Inverter response to a bit pattern test
Filter to suppress brief signals
Description
F-DI changeover tolerance time (factory setting: 500 ms)
Tolerance time to change over the fail-safe digital input for the basic functions.
STO debounce time (factory setting: 1 ms)
Debounce time of the fail-safe digital input for the basic functions.
Advanced commissioning
6.14 Safe Torque Off (STO) safety function
241