Siemens SINAMICS G120 Operating Instructions Manual page 208

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.5 Drive control via PROFIBUS or PROFINET
● IND, bit 8 ... 15 (subindex): = 1 hex (CDS1 = index1)
● IND, bit 0 ... 7 (page index): = 0 hex (offset 0 ≙ 0 hex)
● PWE1, bit 0 ... 15: = 2D2 hex (722 = 2D2 hex)
● PWE2, bit 10 ... 15: = 3F hex (drive object - for SINAMICS G120, always 63 = 3f hex)
● PWE2, bit 0 ... 9: = 2 hex (index of parameter (DI 2 = 2))
Figure 6-16
Telegram, to assign DI 2 with ON/OFF1
208
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD