Siemens SINAMICS G120 Operating Instructions Manual page 401

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

10.After loading, check whether the inverter outputs alarm A01028.
– Alarm A01028:
– No alarm A01028: Proceed with the next step.
11.Switch off the inverter power supply.
12.Wait until all LEDs on the inverter go dark.
13.Switch on the inverter power supply again.
The inverter reports the faults F01641, F01650, F01680 and F30680. Ignore these faults,
as they will be automatically acknowledged by the following steps.
14.Set p0010 to 95.
15.Set p9761 to the safety password.
16.Set p9701 to AC hex.
17.Set p0010 to 0.
18.Back up the settings so they are not lost when the power fails:
– BOP-2 in the menu "EXTRAS" - "RAM-ROM".
– IOP in the menu "SAVE RAM TO ROM".
19.Switch off the inverter power supply.
20.Wait until all LEDs on the inverter go dark.
21.Switch on the inverter power supply again.
22.Perform a reduced acceptance test.
(Page 416)
You have replaced the Control Unit and transferred the safety function settings from the
Operator Panel to the new Control Unit.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
The loaded settings are not compatible with the inverter.
Clear the alarm with p0971 = 1 and recommission the drive.
Reduced acceptance after component replacement and firmware change
Corrective maintenance
9.2 Replacing inverter components
401