Siemens SINAMICS G120 Operating Instructions Manual page 62

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.3 Installing Power Modules
Table 4-6
Frame
size
FSD
FSE
FSF
You can mount the Power Modules without any lateral cooling air clearance. For tolerance reasons,
1)
we recommend a lateral clearance of approx. 1 mm.
62
Drilling dimensions, cooling air clearances [mm] and fixing [Nm]
Drilling dimensions
h
b
c
430
170
15
509
230
11
680
270
13
Cooling air clearances
Top
Bottom
Front
300
350
300
350
300
350
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
Mounting
1)
Screws/torque
100
4 x M5 / 6
100
4 x M6 / 10
100
4 x M8 / 25

Advertisement