Three-Wire Control, Method 2 - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.4.5

Three-wire control, method 2

Figure 6-10
The "Enable" command is a precondition for switching on the motor. The "ON" command
switches the motor on. The "Reversing" command inverts the motor direction of rotation.
Removing the enable switches the motor off (OFF1).
Table 6-20
Enable / OFF1
Table 6-21
Parameter
p0015 = 20
Table 6-22
Parameter
p3330[0 ... n] = 722.x
p3331[0 ... n] = 722.x
p3332[0 ... n] = 722.x
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
6.4 Controlling clockwise and counter-clockwise rotation via digital inputs
Three-wire control, method 2
Function table
ON
0
0 or 1
1
0→1
1
0→1
Select three-wire control, method 2
Description
Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI 0: Enable / OFF1
DI 1: ON
DI 2: Reversing
Changing the assignment of the digital inputs
Description
BI: 2/3 wire control command 1 (enable/OFF1)
BI: 2/3 wire control command 2 (ON)
Example: p3331 = 722.0 ⇒ DI 0: ON command
BI: 2/3 wire control command 3 (reversing)
Reversing
Function
0 or 1
OFF1: The motor stops.
0
ON: Clockwise motor rotation.
1
ON: Counter-clockwise motor rotation.
Advanced commissioning
195