Table 10-19 PM240-2, IP20, Frame Size D, 3-ph. AC 380 V ... 480 V
Article no. without filter
Article no. with filter
LO base load output
LO base load input current
LO base load output current
HO base load output
HO base load input current
HO base load output current
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Table 10-20 PM240-2, IP20, Frame Size E, 3-ph. AC 380 V ... 480 V
Article no. without filter
Article no. with filter
LO base load output
LO base load input current
LO base load output current
HO base load output
HO base load input current
HO base load output current
Fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
6SL3210-1PE27-5UL0
6SL3210-1PE27-5AL0
37 kW
70 A
75 A
30 kW
62 A
60 A
3NA3830 (100 A)
100 A
1.09 kW
1.10 kW
55 l/s
17 kg
18.5 kg
6SL3210-1PE28-8UL0
6SL3210-1PE28-8AL0
45 kW
86 A
90 A
37 kW
78 A
75 A
3NA3832 (125 A)
125 A
1.29 kW
1.30 kW
83 l/s
26 kg
28 kg
10.4 Technical data, PM240-2 Power Module
6SL3210-1PE31-1UL0
6SL3210-1PE31-1AL0
55 kW
104 A
110 A
45 kW
94 A
90 A
3NA3836 (160 A)
150 A
1.65 kW
1.67 kW
83 l/s
26 kg
28 kg
Technical data