Siemens SINAMICS G120 Operating Instructions Manual page 462

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
10.6 Technical data, PM230 Power Module
Article no. - without filter
Article no. - with filter
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC / UL
Fuse according to UL, Class J
Circuit breaker N3RV2711-1KD10
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Table 10-40 PM230, PT, frame size A, 3 AC 380 V ... 480 V
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC / UL
Fuse according to UL, Class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Table 10-41 PM230, IP20, frame size B, 3-phase 380 ... 480 VAC
Article no. - without filter
Article no. - with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC / UL
Fuse according to UL, Class J
462
6SL3210-1NE17-7UG1
6SL3210-1NE17-7AG1
7.7 A
2.2 kW
6.1 A
5.9 A
3NE1813-0
10 A
12.5 A
0.11 kW
4.5 l/s
1.4 kg
1.6 kg
6SL3211-1NE17-7UG1
6SL3211-1NE17-7AG1
3 kW
8.0 A
7.7 A
2.2 kW
6.1 A
5.9 A
3NE1813-0
10 A
0.11 kW
4.5 l/s
1.7 kg
1.9 kg
6SL3210-1NE21-0UG1
6SL3210-1NE21-0AG1
4 kW
10.5 A
10.2 A
3 kW
8.0 A
7.7 A
3NE1813-0
15 A
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
6SL3210-1NE21-3UG1
6SL3210-1NE21-3AG1
5.5 kW
13.6 A
13.2 A
4 kW
10.5 A
10.2 A
3NE1814-0
20 A
Converter with the CU240B-2 and CU240E-2 Control Units
6SL3210-1NE21-8UG1
6SL3210-1NE21-8AG1
7.5 kW
18.6 A
18 A
5.5 kW
13.6 A
13.2 A
3NE1815-0
25 A

Advertisement

Table of Contents
loading