Automatic Restart - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converters chassis devices with cu240b-2 and cu240e-2
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

6.27

Automatic restart

The automatic restart includes two different functions:
● The inverter automatically acknowledges faults.
● After a fault occurs or after a power failure, the inverter automatically switches-on the motor
again.
The inverter interprets the following events as power failure:
● The inverter signals fault F30003 (undervoltage in the DC link), after the inverter line voltage
has been briefly interrupted.
● All of the inverter power supplies have been interrupted - and all of the energy storage
devices in the inverter have discharged to such a level that the inverter electronics fail.
Setting the automatic restart function
Danger to life as a result of machine parts unexpectedly starting
When the "automatic restart" function is active (p1210 > 1), the motor automatically starts
after a power failure. Unexpected movement of machine parts can result in serious injury and
material damage.
● Block off hazardous areas within the machine to prevent inadvertent access.
If it is possible that the motor is still rotating for a longer period of time after a power failure or
after a fault, then you must also activate the "flying restart" function.
Using p1210, select the automatic restart mode that best suits your application.
Figure 6-66
Automatic restart modes
The principle of operation of the other parameters is explained in the following diagram and in
the table below.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2017, FW V4.7 SP6, A5E34259001B AD
WARNING
Flying restart – switching on while the motor is running (Page 333)
Advanced commissioning
6.27 Automatic restart
335

Advertisement

Table of Contents
loading

Table of Contents