S4If Control Circuit Terminal Diagrams - Magnetek Impulse G+ series 4 Instruction Manual

Adjustable frequency crane controls
Hide thumbs Also See for Impulse G+ series 4:
Table of Contents

Advertisement

Classification
Terminal
FM
Analog
Output Signal
AC
AM
RP
Pulse I/O
Signal
MP
R+
R-
RS-485/422
S+
S-
IG
H1
H2
HC
Safe Disable
DM+
DM-

S4IF Control Circuit Terminal Diagrams

Figure 3-14: S4IF Control Circuit Terminal Diagram (120 VAC, 42–48 VAC, 24 VAC)
Signal Function
Multi-function analog output (H04-
MFAO 1
01 to H04-03)
Analog Common
Analog signal common
Multi-function analog output 2
MFAO 2
(H04-04 to H04-06)
Multi-Function Pulse
Pulse input frequency reference
Train Input
(H06-01)
Pulse train output
Pulse output frequency (H06-06)
(Output frequency)
Receive (+)
Receive (-)
For 2-wire RS-485, jumper R+ and
S+ and jumper R- and S-
Transmit (+)
Transmit (-)
Shield connection
Serial Communication Shield
Safe Disable input 1
• One or both open: Motor Output
Disabled
Safe Disable input 2
• Both closed: normal operation
Safe Disable
common
• Off time of at least 1ms
Safety monitor output Outputs the status of the Safe
Disable function. Closed when
Safety monitor output
both Safe Disable channels are
common
closed.
Figure 3-15: S4IF Control Circuit Terminal Diagram (24 VDC)
Description
IMPULSE®•G+ & VG+ Series 4 Instruction Manual - February 2017
Signal Level
-10 to +10V, 2 mA
0 to +10V, 2 mA
4 to 20 mA
0V
-10 to +10V, 2 mA
0 to +10V, 2 mA
Input Freq.: 0 to 32 kHz
Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 VDC
Low Level: 0 to 0.8 VDC
Input Impedance: 3kΩ
32 kHz (max)
RS-485/422 Line Driver
115.2 kbps (max)
0V
24 VDC, 8 mA
Internal Impedance: 3.3kΩ
48 VDC, 8 mA
3-21