Serial Communication Set-Up - Magnetek Impulse G+ series 4 Instruction Manual

Adjustable frequency crane controls
Hide thumbs Also See for Impulse G+ series 4:
Table of Contents

Advertisement

Serial Communication Set-up

The IMPULSE
RTU (RS-485/422) protocol. Cycle power after changing serial format parameters.
Parameter
H05-01
H05-02
H05-03
H05-04
H05-05
H05-06
H05-07
H05-09
H05-10
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-102
®
•G+ and VG+ Series 4 uses terminals R
Table 5-85: Serial Communication Set-up Parameter Settings
Display
Function
Serial Comm Adr
Serial communication address
Serial Baud Rate
Sets the baud rate
0
1200 bps
1
2400 bps
2
4800 bps
3
9600 bps
4
19.2 kbps
5
38.4 kbps
6
57.6 kbps
7
76.8 kbps
8
115.2 kbps
Cycle power for the setting to take effect.
Serial Com Sel
Sets the parity type
0
No Parity
1
Even Parity
2
Odd Parity
Cycle power for the setting to take effect.
Serial Fault Set
Determines stopping method
when a serial fault occurs.
0
Decel to Stop
1
Coast to Stop
2
Fast Stop
3
Alarm Only
Serial Flt Dtct
Determines whether Serial Fault
Detection is enabled
0
Disabled
1
Enabled
Transmit WaitTIM
Send waiting time
RTS Control Sel
RTS Control enable/disable
0
Disabled
RTS is always on
1
Enabled
RTS is ON only when sending
CE Detect Time
Sets the time required to detect a
communications error. Adjustment
may be needed when networking
several drives.
CommReg 25h Unit
Selects the units for the output
voltage monitor value in Modbus
Register 0025H.
0
0.1V
1
1V
+
-
+
-
/R
, S
/S
to communicate the MODBUS
Range
00–FF
0–8
0–2
0–3
0, 1
5–65 ms
0, 1
0.0–10.0 sec
0, 1
Default
1F
3
0
0
1
5
1
2.0
0