Stop Method

B03-03 selects the stopping method suitable for the particular application.
Parameter
Display
B03-03
Stopping Method
0
Decel to Stop
1
Coast to Stop
4
Decel with timer
(Traverse mode
only)
6
No Load Brake
* Initial value is determined by X-Press Programming (Table 4-6, 4-7, or 4-8 on pages 4-12, 4-13, and 4-14).

Decel to Stop (B03-03=0)

Upon removal of the FWD or REV run command, the motor decelerates at a rate determined by the
time set in deceleration time 1 (B05-02) and DC injection braking is applied after the DC injection
start frequency D01-01 has been reached. If the deceleration time is set too short or the load inertia
is too large, an overvoltage fault (OV) or deviation (DEV) may occur during deceleration. In this case,
increase the deceleration time or install an optional braking transistor and/or braking resistor.
Table 5-5: Stop Method Parameter Settings
Function
Determines stop method.
(Fig 5-2)
(Fig 5-3)
(Fig 5-4)
See No-Load Brake Parameter
Group C8.
Figure 5-2: Decel to Stop
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
Range
Default Model
0, 1, 4, 6
G+: 0*
VG+: 6*
G+/VG+
G+/VG+
G+/VG+
VG+
5-7