Copy Function

Parameter
O04-01
O04-02
O04-07
The digital operator has parameter COPY capabilities via built-in non-volatile memory. The digital
operator can READ all of the parameters in the Drive and store them for later, and then WRITE back
to the Drive or into a Drive with the same product code and software number. In order to read the
parameter values and store them into the digital operator, select O04-02 = 1 (Enabled). If you
attempt to READ the data, which overwrites any previously stored data, without first setting
O04-02 = "1: Enabled," you will get the following error:
After setting O04-02 = 1 (Enabled), it is possible to store parameter values in the digital operator by
setting O04-01 = 1 (INV  OP READ). A successful READ of the parameter values will display:
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-128
Table 5-110: Copy Function Parameter Settings
Display
Function
Copy Function Sel
Copy parameters to/from keypad
0
COPY SELECT
1
INV
OP READ
Drive

2
OP
INV WRITE
Keypad
3
OP ↔ INV VERIFY Keypad ↔ Drive
Read Allowable
Enables/disables copy function
0
Disabled
1
Enabled
ChrgCircMaintSet
Sets the value of the Maintenance
Monitor for the soft charge bypass
relay. See U04-06 to check when
the bypass relay may need to be
replaced.
Keypad
Drive
RDER
READ DATA ERROR
END
READ COMPLETE
Range
Default
0–3
0
0, 1
1
0–150%
0