Digital Outputs

The IMPULSE
various conditions. Drive digital output capabilities can be increased with the installation of an S4IO
or DO-A3 option card. The following table lists the function selections for the multi-function digital
outputs and indicates the control methods during which each function can be enabled.
Parameter
H02-01
H02-02
H02-03
H02-06
* Initial value is determined by X-Press Programming (Table 4-6, 4-7, or 4-8 on pages 4-12, 4-13, and 4-14).
Table 5-76: Multi-Function Digital Outputs (MFDO) selectable for H02-0x and F05-0x
Display
0
Brake Release*
1
Zero Speed*
2
Fref/Fout
Agree1
3
Fref/Set Agree 1 ON/CLOSED: When the output frequency (U01-02) is within L04-01 ± L04-02
4
Freq Detect 1
5
Freq Detect 2
6
Inverter Ready*
7
DC Bus
Undervolt*
8
BaseBlock
9
Operator Ref
A
Brake 2
B
Trq Det 1 N.O.
* This output does not have an inverse output
** Contact will open when power is disconnected
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-90
®
•G+ and VG+ Series 4 has three built-in multi-function digital outputs for indicating
Table 5-75:
Digital Outputs Parameter Settings
Display
Function
Term M0-M1 Sel
Digital Output 1 Function
(Reference Table 5-76)
Term M2-M3 Sel
Digital Output 2 Function
(Reference Table 5-76)
Term M5-M6 Sel
Digital Output 3 Function
(Reference Table 5-76)
Wh Disp Units
Watt Hour Output Unit Selection
0
0.1 kWh units
1
1 kWh units
2
10 kWh units
3
100 kWh units
4
1000 kWh units
Function
ON/CLOSED: When the drive is commanding the brake to be Open
OFF/OPEN: When the drive is commanding the brake to be Closed
ON/CLOSED: When Motor Speed < D01-01 or E01-09
ON/CLOSED: When the output frequency (U01-02) is within the frequency reference
(U01-01) ± L04-02
OFF/OPEN: When the output frequency or motor speed is not within the frequency
reference (U01-01) ± L04-02
OFF/OPEN: When the output frequency (U01-02) is not within L04-01 ± L04-02
See the "Frequency Detect" section on page 5-109.
See the "Frequency Detect" section on page 5-109.
ON/CLOSED: After the drive has performed initialization process and no faults or
programming mode is detected
ON/CLOSED: When the DC Bus voltage falls below the trip level set in L02-05
ON/CLOSED: During BaseBlock - No Voltage output
OFF/OPEN: When drive is not in a BaseBlock state - Voltage Output
ON/CLOSED: When frequency reference is from the operator
OFF/OPEN: When frequency reference is not from the operator (i.e. external terminals)
ON/CLOSED: When the drive is commanding the secondary brake to be Open
OFF/OPEN: When the drive is commanding the secondary brake to be Closed
ON/CLOSED: When the output current/torque exceeds the value set in parameter L06-
02 for longer than the time set in parameter L06-03.
OFF/OPEN: When the output current/torque does not exceed the value set in
parameter L06-02 for longer than the time set in parameter L06-03.
Range
Default
0–1FF
*
0–1FF
*
0–1FF
*
0–4
0