S4IF Interface Specifications

®
IMPULSE
the S4IF interface board. This eliminates the need for an additional interface relay or isolation
circuitry. The S4IF comes in 24 VDC, 24 VAC (50/60 Hz), 42 to 48 VAC (50/60 Hz), and 120 VAC
(50/60 Hz) options.
The S4IF has eight optically isolated input terminals which can be used to connect the user input
device to the drive. The eight terminals are multi-function terminals, and are used for speed control
and other controls.
The drive has four 250 VAC, 1.0 Amp relays for output devices. It includes three programmable
multi-function output terminals, and a fault output terminal.
NOTE:
* Not certified for CE compliance.

S4I and S4IO Option Specifications

®
IMPULSE
(S4IO) options. The options expand the I/O capability of the drives, without the need for interface
relays or isolation circuitry.
The S4I has four optically isolated input terminals. The S4IO has four optically isolated input
terminals and four dry contact form A relays.
* Not certified for CE compliance.
IMPULSE®•G+ & VG+ Series 4 Instruction Manual - February 2017
1-12
•G+ & VG+ Series 4 is designed to interface with user input and output devices through
The 250 VAC relays must be derated to 48 VAC to comply with CE.
S4IF Model
S4IF-120A60*
S4IF-48A60
S4IF-24A60
S4IF-24D00
•G+ & VG+ Series 4 is compatible with AC digital input (S4I) and AC digital input/output
S4I Model
S4I-120A60*
S4I-48A60
S4I-24A60
Table 1-7: S4IF Ratings
S1-S8
Voltage
120 VAC
42–48 VAC
24 VAC
24 VDC
Table 1-8: S4I Ratings
Voltage
120 VAC
42–48 VAC
24 VAC
Frequency
50/60 Hz
50/60 Hz
50/60 Hz
--
I1-I4
Frequency
50/60 Hz
50/60 Hz
50/60 Hz