Electronic Programmable Limit Switches (EPLS)

Using the motor revolutions (U01-51) from the Height measurement function, it is possible to
program UL1, UL2, LL1, and LL2 positions without the use of rotary limit switches. When C03-16,
C03-17, C03-18, or C03-19 has a value other than 0, the EPLS function will be enabled. Height
measurement must be correctly setup before using EPLS.
Table 5-23: Electronic Programmable Limit Switches Parameter Settings
Parameter
C03-16
C03-17
C03-18
C03-19
NOTE:
A setting of 0 disables that specific limit.
H02-0x or F05-0x =
2B - Upper Limit 1
2C - Upper Limit 2
2D - Lower Limit 1
2E - Lower Limit 2
30 - Lower Limit
31 - Up/Low Limit
Display
Range
UL2 Revolutions
0–65535 Rev
UL1 Revolutions
0–65535 Rev
LL1 Revolutions
0–65535 Rev
LL2 Revolutions
0–65535 Rev
Table 5-24: Limit Switch Outputs
Function
Output ON when keypad displays UL1
Output ON when keypad displays UL2
Output ON when keypad displays LL1
Output ON when keypad displays LL2
Output ON when keypad displays LL1 or LL2
Output ON when keypad displays UL1, UL2, LL1, or
LL2
Figure 5-10: EPLS Parameter Layout