X-Press Programming™

X-Press Programming
when Control Method (A01-02), Motion (A01-03), or Speed Reference (A01-04) are programmed.
These parameters are also added to the Quick-Set menu for fast parameter modification. Reference
tables 4-6, 4-7, and 4-8 for X-Press

Motion (A01-03)

Set this parameter to match the motion of application. See X-Press Programming (Table 4-6, 4-7, or
4-8 on pages 4-12, 4-13, and 4-14) for details.
Setting
0
1
2
4

Speed Reference (A01-04)

This parameter will automatically define the input terminals for the selections listed below. See X-
Press Programming (Table 4-6, 4-7, or 4-8 on pages 4-12, 4-13, and 4-14) for details.
Setting
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
4-10
TM
automatically configures several commonly used parameters and features
TM
Table 4-3: Select Motion Settings
Description
Traverse
Standard Hoist - G+ Default
Hoist NLB - VG+ Default
Braketronic
Table 4-4: Speed Reference Settings
Description
0
2-SPD Multi-Step — Defines Terminal S3 = 2nd speed.
1
3-SPD Multi-Step — Defines Terminals S3 and S4 as speeds 2 and 3
respectively (default).
2
5-SPD Multi-Step — Defines Terminals S3-S6 as speeds 2–5.
3
2-Step Infinitely Variable — Terminals S1 and S2 use B01-01 and speed hold.
Terminal S3 = Accelerate.
4
3-Step Infinitely Variable — Terminals S1 and S2 use B01-01. Terminal S3 =
Speed Hold. Terminal S4 = Accelerate.
5
Uni-Polar Analog — Terminals S1 and S2 = A directional input. Terminal A1 = 0-
10V. Terminal A2 = 4-20mA (when using Terminal A2, set H03-02 to 1F and
H03-10 to 0).
6
Bi-Polar Analog — Terminal S1 = Run Command. Terminal A1 = direction and
frequency -10 to +10VDC.
7
Industrial Coms Sets all terminals to "Not Used". Speed and Run commands
come from optional communication card.
8
RS485/RDSI Coms Sets all terminals to "Not Used." Speed and Run commands
come from serial communications.
Programming defaults.