Anti-Shock

Anti-Shock is a Hoist NLB feature on the IMPULSE
method. The torque output of the hoist is continuously monitored, and when it increases above a
threshold (C07-15 and C07-16), the hoist automatically decelerates and waits for the torque to
stabilize before smoothly re-accelerating (C07-17 and C07-18). Anti-Shock is designed to maximize
hoist operational efficiency while minimizing crane structure fatigue.
Initial Setup and Adjustment
1. Choosing an option to enable/disable Anti-Shock:
a. Setting C07-12 to 0 (Disabled) ensures Anti-Shock does not function.
b. Setting C07-12 to 1 (Enabled) allows Anti-Shock to run always.
c. Setting C07-12 to 2 (Enbl, Not In MSpd) will block Anti-Shock when Micro-Speed is enabled.
d. Setting H01-xx to 4B (Anti-Shock OFF) sets a digital input which, when enabled, will block
Anti-Shock. This allows Anti-Shock to be enabled or disabled by an external input.
2. Run the hoist, unloaded, in the UP direction. Note the value of U01-09 and enter that
approximate value into C07-23.
To make Anti-Shock less sensitive to light loads and more sensitive to heavy loads:
1. Increasing C07-15 (Torque Delta) to a higher percentage increases the torque spike magnitude
that is required to trigger Anti-Shock.
2. Increasing C07-16 (Detection Time) to a higher time widens the window of time that a torque
spike is looked for.
To make Anti-Shock more sensitive to light loads:
1. Decreasing C07-15 (Torque Delta) to a lower percentage lowers the torque increase magnitude
that is required to trigger Anti-Shock.
2. Increasing C07-16 (Detection Time) to a higher time widens the window of time that a torque
spike is looked for.
Troubleshooting
Anti-Shock is triggered when the load is already in the air:
Cause: This is caused by a torque increase due to acceleration, which falls within the parameter
settings for triggering Anti-Shock.
Corrective Action:
1. Increasing C07-14 (Re-Accel Delay) to a higher time may help remedy this occurrence.
2. Increasing C07-15 (Torque Delta) and decreasing C07-16 (Detection Time) will require a higher
torque spike to occur in a shorter amount of time.
When Anti-Shock is triggered, the drive faults to an OV (Overvoltage) or OC (Overcurrent):
Cause: By default, Anti-Shock is configured to decelerate very quickly when a torque increase is
detected. The deceleration rate may cause a rapid increase in voltage or current, which may fault the
drive.
Corrective Action:
1. Increasing C07-18 (Smoothing Decel) will increase the time it takes for the drive to decelerate
directly after the torque spike is detected. Spikes in voltage and/or current will be reduced.
®
•VG+ Series 4 drive in the Flux Vector control