Assessing the System Requirements
It is important to know how the drive will be utilized before working on installation and wiring. Please
know the requirements for the following components:
•
Speed control method(s) - i.e. stepped, stepless, infinitely variable
•
Braking method(s) - coast to stop, decel to stop, No Load Brake (NLB) Hoist
•
Power source voltage, number of phases, and kVA rating
•
Power source location
•
Wire size
•
Grounding location and method
•
Control wiring sources - i.e. cab, pendant, radio
Assessing the Drive Environment
When choosing a location for IMPULSE
1. Ensure that a three-phase 200 to 240 VAC 50/60 Hz power supply is available for a 230 VAC-
rated drive, a three-phase 380 to 480 VAC 50/60 Hz power supply is available for a 460 VAC-
rated drive, and a 500 to 600 VAC 50/60 Hz power supply is available for a 575 VAC-rated drive.
2. Ensure the encoder is supplied with +5 VDC or 12 VDC.
3. If the RMS encoder current requirement is greater than 200 mA, provide an auxiliary power
supply to the encoder.
4. Ensure that the drive-to-motor wiring distance is less than 150 ft. unless appropriate reactors,
filters, and/or inverter duty motor is used.
5. Ensure that the drive circuit wiring is protected or isolated from:
•
Ambient temperatures outside the range of +14°F to +140°F (-10°C to +60°C) at 2 kHz
carrier frequency.
•
Rain or moisture
•
Corrosive gases or liquids
•
Direct sunlight
•
Severe mechanical vibration
6. Ensure that the drive is housed in an appropriate NEMA-rated enclosure.
7. For severe-duty applications (long lifts, for example) or with 75-HP-or-greater motors, ensure
that the drive control system (including dynamic braking resistors) is adequately cooled, even
though the ambient temperature limit is not exceeded. For more information, contact Magnetek.
®