Motor Set-up

E2 constants define motor parameters. Normally, the default settings for E2 constants are
determined by kVA selection (O02-04). In flux vector control and open loop vector, the E2 constants
will be set automatically during auto-tuning. At minimum, the motor rated current should be entered
into E02-01.
If rotational auto-tuning cannot be performed, E02-02 and E02-05 can be calculated using the
motor's nameplate information or by performing non-rotational auto-tuning.
Motor rated slip frequency (E02-02) can be calculated by using the following equation:
Motor terminal resistance E02-05 can be calculated by using the following equation:
r
W here...
Parameter
Display
E02-01
Motor Rated FLA
E02-02**
Motor Rated Slip
E02-03**
No-Load Current
E02-04
Number of Poles
E02-05**
Term Resistance
E02-06**
Leak Inductance
E02-07**
Saturation Comp 1
E02-08**
Saturation Comp 2
E02-09**
Mechanical Loss
E02-10**
Motor Iron Loss
E02-11
Rated Power
* Initial value is determined by O02-04 (kVA Selection) and D10-01.
** This value is automatically set during auto tuning.
f
f
s
W h ere...
f
: slip freq uency (H z)
s
f: rated frequency (H z)
N: rated m otor speed (rpm )
P: num ber of m otor poles
273
 
r
*
t
p
2 73
r
: m oto r t erm inal resistance
t
r
: Phase-to-P hase resistance at insu lation class tem perature
p
T
: insulation class tem peratu re (°C )
i
Table 5-60: Motor Set-up Parameter Settings
Function
Motor-rated current
Motor-rated slip frequency
Motor no-load current
Number of poles in motor
Motor terminal resistance
Leakage Inductance
Core-Saturation Compensation
Coefficient 1
Core-Saturation Compensation
Coefficient 2
Sets the motor mechanical loss as
a percentage of motor rated power
(HP) for the motor.
Sets the motor iron loss in Watts
for the motor.
Rated output
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
N
* P
120
25
C
T
i
 
2
T
i
Range
Default
*
*
0.00–20.00 Hz
*
0–[(E02-01)-1]
*
2–48
4
0.000–65.000 
*
0.0–40.0%
*
0.00–0.50
0.50
E02-07–0.75
0.75
0.0–10.0%
0.0
0–65535 W
*
0.0–650.0 HP/kW
*
5-73