End of Travel Limits

This function can automatically slow and stop a crane or hoist when it reaches the end of travel
limits. Two types of limit inputs (slowdown and stop) are available in both travel directions. Inputs can
be programmed through the S4IF card.
Parameter
Display
C03-01
UL1 Speed
C03-02
UL1 Decel Time
C03-03
UL2 Stop Time
C03-04
LL1 Speed
C03-05
LL1 Decel Time
C03-06
LL2 Stop Time
C03-07
Lmt Stop Method
0 Decel to Stop
1 Coast to Stop
2 Use B3-03 Method
C03-08
UL3 Stop Method
0 Decel / Alarm
1 Coast / Alarm
2 Use B3-03/Alarm
3 Decel / Fault
4 Coast / Fault
5 Use B3-03/Fault
C03-09
UL3 Decel Time
* Initial value is determined by X-Press Programming (Table 4-6, 4-7, or 4-8 on pages 4-12, 4-13, and 4-14).
** Range is extended to 0.0–6000.00 when B05-16 = 1.
Table 5-18: End of Travel Limits Parameter Settings
Function
Speed when UL1 is detected
Decel time when UL1 is detected
Decel time to STOP when UL2 is
detected
Speed when LL1 is detected
Decel time when LL1 is detected
Decel time to STOP when LL2 is
detected
Determines the stopping method
when UL2 or LL2 is detected
Weight Limit Stop Method for H01-
xx = 12 or 62. Action is Alarm only
when inverter is not running.
Decel to Stop with Alarm (no
further raise allowed)
Coast to Stop with Alarm (no
further raise allowed)
Use B03-03 to Stop with Alarm (no
further raise allowed)
Decel to Stop with Fault
Coast to Stop with Fault
Use B03-03 to Stop with Fault
Sets the deceleration time when
H01-xx = 12 or 62
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
Range
Default
0.00–E01-04 Hz
6.00
0.0–25.5 sec**
1.0
0.0–25.5 sec**
1.0
0.00–E01-04 Hz
6.00
0.0–25.5 sec**
1.0
0.0–25.5 sec**
1.0
0-2
2*
0-5
4
0.0–25.5 sec
1.0
5-19