Test Mode Configuration

Test Mode is a troubleshooting aid that is intended for troubleshooting Flux Vector control method
problems in the field. This feature cannot be left on indefinitely, as it will generate a fault after being
on for a total accumulated time of ten minutes. At this time, the fault must be reset or the power must
be cycled.
To enable Test Mode, refer to parameter L05-01.
Table 5-61: Test Mode Configuration Parameter Settings
Parameter
E03-01
E03-02
E03-03
E03-04
E03-05
E03-06
E03-07
E03-08
E03-09
E03-10
E03-11
E03-12
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-74
Display
Function
Control Method
Control Method.
0
V/f Control
2
Open Loop Vector
Stopping Method
Deceleration Method
0
Decel to Stop
1
Coast to Stop
Max Frequency
Maximum Frequency
Max Voltage
Maximum Voltage
Base Frequency
Motor Base Frequency
Mid Frequency A
Motor Middle output frequency
Mid Voltage A
Motor Middle output frequency
voltage
Min Frequency
Minimum Frequency
Min Voltage
Motor Minimum output frequency
voltage
Mid Frequency B
Midpoint Output Frequency B
Mid Voltage B
Midpoint Output Voltage B
Base Voltage
Motor Base Voltage
Range
Default
0, 2
2
0, 1
1
40.0–150.0 Hz
60.0
230 V: 0.0–255.0
Determined
by O02-04
460 V: 0.0–510.0
575 V: 0.0–733.1
0.0–150.0 Hz
60.0
0.0–150.0 Hz
Determined
by E01-03
230 V: 0.0–255.0
Determined
by E01-03
460 V: 0.0–510.0
575 V: 0.0–733.1
0.0–150.0 Hz
Determined
by E01-03
230 V: 0.0–255.0
Determined
by E01-03
460 V: 0.0–510.0
575 V: 0.0–733.1
0.0–150.0 Hz
0.0
230 V: 0.0–255.0
0.0
460 V: 0.0–510.0
575 V: 0.0–733.1
230 V: 0.0–255.0
0.0
460 V: 0.0–510.0
575 V: 0.0–733.1