Pulse Train Input/Output

Pulse Input and Output provides speed control capabilities via the RP and MP terminals.
Parameter
H06-01
H06-02
H06-03
H06-04
H06-05
H06-06
H06-07
H06-08
H06-09
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-104
Table 5-86: Pulse Input/Output Parameter Settings
Display
Function
Pulse Input Sel
Selects the function of pulse input
terminal RP.
0
Frequency Ref
Set B03-01 = 4 (pulse input) to
enable this input.
5
Simple PG
OLV Control with Simple PG
feedback (possible only when
using motor 1 in Hoist NLB).
6
PG Feedback
PG-X3 pulse feedback into the RP
terminal coming from a Slave
drive.
7
RP Feedback
Pulse feedback into the RP
terminal coming from a Slave
drive.
Pulse In Scale
Number of pulses equal to the
maximum output frequency
Pulse Input Gain
Sets the output level when input is
100%
Pulse Input Bias
Sets the output level when input is
zero Hz.
Pulse In Filter
Sets the input filter time constant
Pulse Output Sel
Selects the function of pulse
output terminal MP.
000 Not Used
101 Frequency Ref
102 Output Freq
105 Motor Speed
120 SFS Output
Pulse Out Scale
Item output by pulse monitor is
selected by corresponding U01-xx
value.
Pulse Min Freq
Sets the minimum frequency for
the pulse train input to be
detected. Enabled when
H06-01 = 0.
Pulse Dev Detect
When the Pulse Input terminal RP
(H06-01) is programmed for PG
Feedback (6) or RP Feedback (7),
the pulse input from terminal RP is
compared to the pulse output of
terminal MP. If the difference is
greater than the percentage
programmed into H06-09, the
drive will fault and display
"PULSDEV" on the keypad
display.
Range
Default
0, 5–7
0
1000–32000 Hz
1440
0.0–1000.0%
100.0
-100.0–100.0%
0.0
0.00–2.00 sec
0.10
0–120
102
0–32000 Hz
1440
0.1–1000.0 Hz
0.5
0.0–25.5%
5.0