Lower Limit/Upper Limit Bypass MFDI

The Limit Bypass allows for the following without the use of jumpers or re-programming of the drive
parameters:
1. Ease of testing of the Weighted Upper Limit Switch (UL3) or re-homing the Height
Measurement function, and
2. To allow changing of the wire ropes, i.e. spooling all the rope off of the hoist drum.
NOTE:
The momentary key-switch to operate this function should only be accessible to
maintenance personnel, not the crane operator. A functional description and usage
procedure should be included in an administrative control program to avoid confusion and
potentially have the End of Travel Limit switches left in a bypassed state during normal
operation of the crane.
Functions Bypassed
Upper Limit 1 N.O. (MFDI = 06)
Upper Limit 2 N.O. (MFDI = 07)
Lower Limit 1 N.O. (MFDI = 08)
Lower Limit 2 N.O. (MFDI = 09)
Upper Limit 1 N.C. (MFDI = 0A)
Upper Limit 2 N.C. (MFDI = 0B)
Lower Limit 1 N.C. (MFDI = 0C)
Lower Limit 2 N.C. (MFDI = 0D)
UL2 detected by EPLS (C03-16)
UL1 detected by EPLS (C03-17)
LL1 detected by EPLS (C03-18)
LL2 detected by EPLS (C03-19)
×
= Limit Bypass
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-24
Table 5-25: Monitor Values at Hook Height Home Position
C03-14
U01-51
0
0
1
C03-13
2
0
3
C03-13
4
0
Table 5-26: Limit Bypass MFDI
C09-0x or H01-0x settings will bypass the functions in the left
C03-15 = 0
C03-15 = 1
U01-50
0%
100%
0%
100%
0%
most column when the input is activated
73
×
×
×
×
×
×
U01-50
100%
0%
100%
0%
100%
74
×
×
×
×
×
×
×
×
×
×
×
×