Configuring the Swift-Lift & Ultra-Lift Function
For 2, 3, 5-Speed Multi-Step (A01-04 = 0, 1, or 2):
1. Set C06-01= 1–4 to enable the Swift-Lift & Ultra-Lift Function, 1 = Enable Automatic, 2 =
Enable by Multi-Function Digital Input (MFDI), 3 = Enable Adaptive (Ultra-Lift Only), 4 = Adaptive
by MFDI (Ultra-Lift Only).
2. Set C06-02 and C06-03 to determine Swift-Lift & Ultra-Lift maximum FWD/REV output
frequency.
3. Set C06-04 and C06-05 to determine Swift-Lift & Ultra-Lift maximum enable output current.
4. Set the Swift-Lift & Ultra-Lift Enabling Speed (C06-06) one or two hertz below the maximum
normal running speed reference.
For example: If the maximum normal running speed is at 60 Hz, set C06-06 to 59 Hz
5. Ensure that the Maximum Frequency (E01-04) is increased from 60 Hz.
For 2, 3 Step Infinitely Variable (A01-04 = 3 or 4)
1. If the system is using 2-Step or 3-Step Infinitely Variable as the Speed Control Method, the
following formula is used to adjust the constant
B02-01 (Reference Upper Limit).
For Uni-Polar/Bi-Polar Analog (A01-04 = 5 or 6)
1. If the system is using Bi-Polar Analog or Uni-Polar Analog as the Speed Control Method, the
following formula is used to adjust the constant
H03-03 (Gain Multiplier for Terminal A1 analog input signal).
H03-11 (Gain Multiplier for Terminal A2 analog input signal).
Motors and drive machinery must be capable of operating above motor base speed. Consult
the motor/gearbox/hoist manufacturer before enabling the Swift-Lift and Ultra-Lift function.
Failure to observe this warning may result in damage to equipment and possible injury or
death to personnel.
IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-32
or 58 Hz as the Swift-Lift & Ultra-Lift Enabling Speed.
WA R N I N G