DVC6200f Digital Valve Controller
AO Function Block
February 2017
Block Errors
Table E‐1 lists conditions reported in the BLOCK_ERR [6] parameter.
Table E‐1. AO BLOCK_ERR Conditions
Condition Number
1
Block Configuration Error ‐ CHANNEL and SHED_OPT set to 0
3
Simulate active ‐ Simulation is enabled and the block is using a simulated value in its execution.
4
Local Override ‐ Device in fault state. Actual mode LO.
Device Fault State Set ‐ AO block in fault state after FSTATE_TIME because of Bad status or IFS substatus on CAS_IN or
5
Resource block commanded fault state.
Device Needs Maintenance Soon ‐ Indicates a Maintenance
6
enabled. See page 67.
8
Output failure ‐ PV has bad status.
Device Needs Maintenance Now ‐ Indicates Failed
13
page 67.
14
Power Up ‐ This condition exists after power up until actual mode is not Out of Service.
15
Out of Service ‐ The block is in Out of Service (OOS) mode.
AO Function Block Parameter List
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shared Index Number indicates sub‐parameter
Table E‐2. Analog Output Function Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
216
Index
RO /
Block
Number
RW
Mode
1
RO
N/A
0 to 65535
2
RW
ALL
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
Condition Name and Description
condition is active if Block Error Reporting is
Field Diagnostic
condition is active if Block Error Reporting is enabled. See
Field Diagnostic
Range
Initial Value
0
Spaces
0
0
Instruction Manual
D103412X012
Description
Data Type: Unsigned16
The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.
Data Type: Octet String
The user description of the intended application of
the block.
Data Type: Unsigned16
The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.