DVC6200f Digital Valve Controller
ISEL Function Block
February 2017
Alarms are grouped into five levels of priority, as shown in table E‐11.
Table E‐11. ISEL Function Block Alarm Priorities
Priority Number
0
The priority of an alarm condition changes to 0 after the condition that caused the alarm is corrected.
An alarm condition with a priority of 1 can be recognized by the system. The device monitors the alarm but does not report it
1
until requested by the host system.
An alarm condition with a priority of 2 is reported to the operator, but generally does not require operator attention (such as
2
diagnostics and system alerts).
3-7
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
8-15
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
1. The priority classes "advise" and "critical" have no relationship to Plant Web Alerts.
Block Errors
Table E‐12 lists conditions reported in the BLOCK_ERR [6] parameter.
Table E‐12. ISEL BLOCK_ERR Conditions
Condition Number
1
14
15
262
Block Configuration Error ‐ If OP_SELECT is not being used, and SELECT_TYPE = 0. This implies OP_SELECT status is good and actual
mode is AUTO.
Power Up ‐ Set if the Target mode is Out of Service when powered up until the mode is changed.
Out of Service ‐ The block is in Out of Service (OOS) mode
(1)
Priority Description
Condition Name and Description
Instruction Manual
D103412X012