Communication Timeout; Options - Fisher FIELDVUEDVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

DVC6200f Digital Valve Controller
Detailed Setup - Resource Block
February 2017

Communication Timeout

Shed Remote Cascade
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your "advanced" control.
Default value for RCas Timeout is 20 seconds.
Shed Remote Cascade (SHED_RCAS [26]) determines how long function blocks in the DVC6200f should wait before
giving up on remote computer writes to RCas parameters. When the timeout is exceeded, the block sheds to the next
mode as defined by the block shed options. If Shed Remote Cascade is set to 0, the block will not shed from RCas.
Enter a positive value in the Shed Remote Cascade field. Time duration is in 1/32 milliseconds (640000
Shed Remote Out
Note
Typically this parameter does not need to be changed. The unit will be operational using the default values assigned by the factory.
Perform this procedure only if a remote computer is sending setpoints from your "advanced" control.
Default value for Shed Remote Out is 20 seconds.
Shed Remote Out (SHED_ROUT [27]) determine how long function blocks in the DVC6200f should wait before giving
up on computer writes to ROut parameters. When the timeout is exceeded, the block sheds to the next mode as
defined by the block shed options. If Shed Remote Out is set to 0, the block will not shed from ROut. Enter a positive
value in the Shed Remote Out field. Time duration is in 1/32 milliseconds (640000

Options

Diagnostic Tier (DIAG_OPTIONS [103]) show which diagnostic options are available in the instrument.
Function Block Options (FB_OPTIONS [102]) show which function blocks are available in the instrument.
Miscellaneous Options (MISC_OPTIONS [104]) indicate which miscellaneous licensing options are enabled.
Features Available (FEATURES [17]) indicates which feature options are available in the resource block.
D Reports enables alert and event reporting. Reporting of specific alerts may be suppressed. See Alerts on page 54.
D Fault State enables the ability of the output block to react to various abnormal conditions by shedding mode. See
parameter descriptions for Set Fault State (SET_FSTATE [29]) and Clear Fault State (CLR_FSTATE [30]) in table 4‐3
and "Action on Fault Detection".
D Write Lock permits using Write Lock (WRITE_LOCK [34]) to prevent any external change to parameter values. Block
connections and calculation results will proceed normally, but the configuration is locked. Also see Write Lock, on
page 23.
24
Instruction Manual
D103412X012
20 secs).
=
20 secs).
=