Fisher FIELDVUEDVC6200f Instruction Manual page 34

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

DVC6200f Digital Valve Controller
Detailed Setup - Resource Block
February 2017
Table 4‐3. Resource Block Parameter Definitions
Label
PARAMETER_NAME
Test Read Write
TEST_RW
DD Resource
DD_RESOURCE
Manufacturer Id
MANUFAC_ID
Device Type
DEV_TYPE
Device Revision
DEV_REV
DD Revision
DD_REV
Grant Deny
GRANT_DENY
GRANT
DENY
Hard Types
HARD_TYPES
Restart
RESTART
34
Index
RO /
Mode
Number
RW
8
ALL
9
RO
N/A
10
RO
N/A
11
RO
N/A
12
RO
N/A
13
RO
N/A
14
0: Program
1: Tune
2: Alarm
14.1
RW
ALL
3: Local
4: Operate
5: Service
6: Diagnostic
0: Program Denied
1: Tune Denied
2: Alarm Denied
14.2
RW
ALL
3: Local Denied
4: Operate Denied
5: Service Denied
6: Diagnostic Denied
0: Scalar Input
1: Scalar Output
15
RO
N/A
2: Discrete Input
3: Discrete Output
1: Run
2: Restart resource
3: Restart with
16
RW
ALL
defaults
4: Restart processor
11: Restart w/Factory
Default Blocks
Initial
Range
Value
This parameter may be used in interoperability
testing to read and write all standard data types
0
supported by the Fieldbus Foundation.
Data Type: Visible String
String identifying the VFD tag of the resource
Spaces
that contains the Device Description for this
resource.
Data Type: Unsigned32
Manufacturer identification number, used by an
interface device or host to locate the DD file for
the resource. All manufacturer identification
numbers are maintained by the Fieldbus
Foundation. A host usually will have a base
directory for DD files. In this directory is a
subdirectory for each manufacturer id. In each
0x5100
manufacturer id subdirectory is a directory for
each device type made by that manufacturer.
The device type directories contain files named
by combining the device revision for the
particular device type with the revision of the
device description. The manufacturer id for
Fisher is 0x005100.
Data Type: Unsigned16
Manufacturer's model number associated with
0x4602
the resource, used by an interface device to
locate the DD file for the resource.
Data Type: Unsigned8
Manufacturer's revision number associated with
Varies with
the resource, used by an interface device to
release
locate the DD file for the resource.
Data Type: Unsigned8
The minimum revision of the device description
1
(DD) that can be used with the device revision of
the instrument.
Data Type: DS‐70
All bits: 0
Options for controlling access of a host
computer and to block parameters. Parameter
contains two attributes Grant and Deny each
with program, tune, alarm and local
permissions. Clearing a grant permission sets
the corresponding deny permission, 0 = N/A,
1 = granted.
Deny permissions may be cleared through the
All bits: 0
Deny attribute but not set, 0 = N/A, 1 = denied.
Data Type: Bit String
0: 1
0 = Inactive
1: 1
1 = Active
2: 1
The types of hardware available as channel
3: 1
numbers in this resource.
Data Type: Unsigned8
Allows a manual restart to be initiated. For
1: Run
details see Restarting the Instrument in this
section.
Instruction Manual
D103412X012
Description

Advertisement

Table of Contents
loading

Table of Contents