DVC6200f Digital Valve Controller
Viewing Device Variables and Diagnostics
February 2017
•Supply Sensor Failure indicates the pressure sensor is reporting a pressure that is significantly outside of the normal
operating pressure, and has failed.
•IOP Failure indicates the I/O processor has failed.
•Drive Current Alert indicates that the Drive Current has exceeded the Drive Current Alert Point for more than the
Drive Current Alert Time.
•Simulate Jumper ON indicates the simulate jumper is connected to the DVC6200f between the two AUX terminals.
Block Error
Table 6‐2 lists conditions reported in the BLOCK_ERR [6] and XD_ERROR [11] parameters.
Table 6‐2. Transducer Block BLOCK_ERR and XD_ERROR Conditions
Condition Number
Block Configuration Error ‐ Indicates that one of the following parameters have been configured out of the proper range: 15,
1
16, 47.1, 47.2, 46.3, 46.5, 42.7, 42.8.
15
Out of Service ‐ Indicates Out of Service Mode.
Device Record
The following parameters are contained in the Device Record menu of the transducer block.
Maximum Temperature (TEMP_MAX [103.1]) shows the maximum temperature the instrument has experienced since
installation.
Maximum Temperature Time (TEMP_MAX_TIME [103.2]) shows the date and time when the Temperature Maximum
occurred.
Minimum Temperature (TEMP_MIN [103.3]) shows the minimum temperature the instrument has experienced since
installation.
Minimum Temperature Time (TEMP_MIN_TIME [103.4]) shows the date and time when the Temperature Minimum
occurred.
Maximum Supply Pressure (SUPPLY_PRESS_MAX [103.5]) shows the maximum supply pressure the instrument has
experienced since installation.
Maximum Supply Pressure Time (SUPP_PRESS_MAX_TIME [103.6]) shows the date and time when the Supply Pressure
Maximum occurred.
Minimum Supply Pressure (SUPP_PRESS_MIN [103.7]) shows the minimum supply pressure the instrument has
experienced since installation.
Minimum Supply Pressure Time (SUPP_PRESS_MIN_TIME [103.8]) shows the date and time when the Supply Pressure
Minimum occurred.