Fisher FIELDVUEDVC6200f Instruction Manual page 322

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

DVC6200f Digital Valve Controller
DI Function Block
February 2017
Table E‐41. Discrete Input Function Block Parameter Definitions
Label
PARAMETER_NAME
Simulate Discrete
SIMULATE_D
SIMULATE_STATUS
SIMULATE_VALUE
TRANSDUCER_STATUS
TRANSDUCER_VALUE
ENABLE/DISABLE
Transducer State
XD_STATE
Output State
OUT_STATE
Grant Deny
GRANT_DENY
GRANT
DENY
I/O Options
IO_OPTS
Status Options
STATUS_OPTS
DI Channel
CHANNEL
Process Value Filter Time
PV_FTIME
Field Value Discrete
FIELD_VAL_D
322
Index
RO /
Block
Number
RW
Mode
9
9.1
ALL
9.2
ALL
9.3
RO
ALL
9.4
RO
ALL
0=Not initialized
9.5
1=Simulation Disabled
2=Simulation Active
10
ALL
11
ALL
12
0: Program
12.1
ALL
1: Tune
2: Alarm
12.2
ALL
3: Local
13
OOS
0: Invert
3=Propagate Failure
14
OOS
Forward
8=Uncertain in MAN mode
0=undefined
23=Valve Position or
Pressure (Discrete)
24= PV > 97%
25= PV < 3%
26=PV Below LO LO limit
27=PV Below LO limit
28=PV Above HI limit
15
OOS
29=PV Above HI HI limit
30=PV Within Proximity of
LO LO
31=PV Within Proximity of
LO
32=PV within Proximity of
HI
33=PV within Proximity of
HI HI
16
ALL
Positive
17
RO
Range
Initial Value
0
0
0
0
1=Simulation
Disabled
0
0
All bits:0
All bits: 0
All bits:0
All bits:0
0=Undefined
0
0
Instruction Manual
D103412X012
Description
Data Type: DS‐83
Allows the transducer discrete input or output
to the block to be manually supplied when
simulate is enabled. When simulation is
disabled, the simulate value and status track
the actual value and status.
Data Type: Uint16
Index to the text describing the states of a
discrete for the value obtained from the
transducer.
Data Type: Unsigned16
Index to the text describing the states of a
discrete output.
Data Type: DS‐70
Options for controlling access of host
computers and local control panels to
operating, tuning, and alarm parameters of
the block.
GRANT: 0=NA, 1=granted
DENY: 0=NA, 1=denied
Data Type: Bit String
0=Disable
1=Enable
Allows you to select how the I/O signals are
processed.
Data Type: Bit String
0=Disable
1=Enable
Options the user may select for the block
processing of status.
Data Type: Unsigned16
Defines the functionality of the discrete input.
See I/O Selection for details. Refer to table
E‐37.
Data Type: Float
Time that FIELD_VAL_D must be in a new
state, before the change is reflected to PV_D
and OUT_D.
Data Type: DS‐66
Raw value of the field device discrete input,
with a status reflecting the transducer
condition.