Alert Reporting; Field Diagnostic Alerts Set Block Status - Fisher FIELDVUEDVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table C‐1. Field Diagnostic Alerts Reporting Requirements
Alert
Drive Current
Drive Signal
Processor Impaired
Output Block Timeout
Block Set to Defaults
Travel Sensor
Output Pressure Sensor
Supply Pressure Sensor
Temperature Sensor
Supply Pressure
Temperature Limit
Travel Deviation
Travel Limit
Cycle Counter
Travel Accumulator
Performance Critical
Performance Reduced
Performance Information
Pressure Fallback

Alert Reporting

For Field Diagnostic alerts to be reported to the operator console, they must pass four tests:
d Alerts must be active
d Reports must be selected in Feature Select
d Alert priority must be greater than 1
d Reporting must not be suppressed for those conditions that caused active alerts.
Features Selected in the Resource block determines if reporting by the instrument is supported. Refer to page 25 for
additional information on Features Selected.
Failed Priority (FAILED_PRI [RB 86]), Maintenance Priority (MAINT_PRI [RB 94]), and Advise Priority (ADVISE_PRI [RB
98]) determine the Field Diagnostic alert priorities. Although 16 priorities are available only three are actually
meaningful for Field Diagnostic alerts. If the priority is 0, no reporting occurs. If the priority is 1, reporting is simulated
within the instrument, but the alert is not actually reported over the bus. The alert condition is reported for priorities 2
through 15, with the higher priorities taking precedence over the lower priorities.
Failed Suppress (FAILED_MASK [RB 92]), Maintenance Suppress (MAINT_MASK [RB 96]), and Advise Suppress
(ADVISE_MASK [RB 100]) determine which of the alert conditions are suppressed so that they are not reported.

Field Diagnostic Alerts Set Block Status

If a Field Diagnostic Alert is active, the AO or DO Block Readback parameter status may change. This behavior is
controlled with the Field Diagnostic Alerts Set PV Status parameter in the transducer block
Transducer Block Mode (Actual)
AUTO
AUTO
Any Mode
Any Mode
Any Mode
AUTO
Any Mode
Any Mode
Any Mode
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
AUTO
DVC6200f Digital Valve Controller
Field Diagnostic Alerts
February 2017
185