Fisher FIELDVUEDVC6200f Instruction Manual page 91

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Group 3 Active
GROUP_3_ACTIVE
PS Event Active
PD_EVENT_ACTIVE
PD Detail 1 Active
PD_DETAIL1_ACTIVE
PD Detail 2 Active
PD_DETAIL2_ACTIVE
Index
RO /
Mode
Number
RW
Bit 18: PST Anomaly
Bit 19: FST Anomaly
Bit 21: PST Success
Bit 22: FST Success
81.3
RO
Bit 23: PST Overdue
Bit 24: FST Overdue
Bit 25: PST Pending
Bit 30: Diagnostic in
Progress
Bit 0: High I/P Drive Signal
Bit 1: Low I/P Drive Signal
Bit 2: High Air Mass Flow
Bit 3: Large Travel
Deviation
Bit 4: Low Supply
Pressure
Bit 5: High Supply
81.4
RO
Pressure
Bit 6: High Crossover
Pressure
Bit 7: Low Crossover
Pressure
Bit 8: No Air Mass Flow
Estimate
Bit 9-16: Reserved
Bit 0: I/P Primary Plugged
Bit 1: I/P Nozzle Plugged
Bit 2: I/P Latched
Bit 4: Relay Jammed
Bit 5: Relay Cross Misadj
Bit 6: Relay Supply Diaph
Leak
Bit 7: Relay Port A Diaph
Leak
Bit 8: Relay Port B Diaph
Leak
Bit 10: Valve Stuck Low
Bit 11: Valve Stuck High
Bit 12: Piston Ring Leak
81.5
RO
Bit 14: Low Supply
Pressure
Bit 15 : External Leak
(High AMF 1a_r)
Bit 16: SOV Trip (High I/P
1q_r or Low I/P 1q_r)
Bit 17: Air Line Blocked
(High I/P 1p_r or Low I/P
1p_r)
Bit 18: Reserved
Bit 19: Reserved
Bit 20: Unknown (High I/P
1x_r or Low I/P 1x_r or
Large Tvl Dev 1x_r)
81.6
RO
Range
Initial Value
Dynamic
All Bits: 0
All Bits: 0
All Bits: 0
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
Data Type: Bit String
0=inactive
1=active
Data Type: Bit String
0=inactive
1=active
Performance Diagnostic event
status.
Data Type: Bit String
0=inactive
1=active
Performance Diagnostic Critical
possible cause.
Data Type: Bit String
0=inactive
1=active
Performance Diagnostic Detail
status.
February 2017
91

Advertisement

Table of Contents
loading

Table of Contents