Simulate Enable Jumper - Fisher FIELDVUEDVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012

Simulate Enable Jumper

WARNING
Personal injury or property damage caused by fire or explosion may occur if this connection is attempted in a potentially
explosive atmosphere or in an area that has been classified as hazardous. Confirm that area classification and atmosphere
conditions permit the safe removal of the terminal box cap before proceeding.
Install a jumper across the SIMULATE ENABLE terminals to enable the instrument to accept a simulate command.
(These terminals are marked AUX on the terminal board, see figure 2‐2). With the jumper in place and the simulate
parameter in the AO or DO block set to enabled, the transducer block ignores the output of the AO or DO block. The
simulate value and status become the readback value and status to the AO or DO block and the transducer block is
ignored. For more information on running simulations, see the Detailed Setup section of this manual, the
Fieldbus specifications, and the host documentation.
WARNING
Removing the jumper will disable the simulate, which may cause the valve to move. To avoid personal injury and property
damage caused by the release of pressure or process fluid, provide some temporary means of control for the process.
DVC6200f Digital Valve Controller
Installation Information
F
February 2017
OUNDATION
15