Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
D The Static Memory Alert is active if a failure occurs in the FRAM memory where the static parameters are stored.
D Static Memory Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [83.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the Static Memory Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
D Static Memory Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [83.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Static Memory Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
D The I/O Processor Alert is active if a failure occurs in the I/O processor.
D I/O Processor Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [83.1]) permits enabling or disabling Self
Test Shutdown. When enabled, and the I/O Processor Alert is active, the transducer Actual mode is placed out of
service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
D I/O Processor Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [83.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused I/O Processor Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service, if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
D Processor Impaired FD Config

Configuration Alerts

Output Block Timeout
D The Output Block Timeout Alert is active if the analog or discrete output block has not executed for longer than the
configured timeout.
D Output Block Timeout Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [83.1]) permits enabling or
disabling Self Test Shutdown. When enabled, and the Output Block Timeout Alert is active, the transducer Actual
mode is placed out of service. The instrument will attempt to drive the valve to the zero power condition and will no
longer execute transducer control function.
D Output Block Timeout Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [83.2]) permits enabling or
disabling Manual recovery from Self Test Shutdown. When enabled, the transducer block will return to Target mode
when the condition that caused Output Block Timeout Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
Manual or Auto. In any case, the target mode will remain Out of Service if the condition that caused the shutdown
remains or until the shutdown trigger is disabled.
D Output Block Timeout (OUTPUT_BLK_TIMEOUT [83.3]) is the maximum time between updates from the AO or DO
block to the transducer block setpoint.
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
February 2017
57