DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
February 2017
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
GROUP_2_ENABLE
GROUP_3_ENABLE
INST_ALERTS_CONFIG
Shutdown Trigger
SHUTDOWN_TRIGGER
Shutdown Recovery
SHUTDOWN_RECOVERY
94
Index
RO /
Mode
Number
RW
Bit 0: Travel Limit Hi Hi
Bit 1: Travel Limit Lo Lo
Bit 2: Travel Limit Hi
Bit 3: Travel Limit Lo
Bit 7: Travel Open
Bit 8: Travel Closed
Bit 9: Proximity Hi Hi
Bit 10: Proximity Hi
Bit 11: Proximity Lo
Bit 12: Proximity Lo Lo
Bit 15: Cycle Counter
Bit 16: Travel
Accumulator
AUTO
Bit 18: LCP Comms
82.2
MAN
Bit 19: LCP Stuck Button
OOS
Bit 20: LCP Demand
Button Pressed
Bit 21: Demand Time
Bit 22: Reset Time
Bit 23: Stroke Open Time
Bit 24: Stroke Closed
Time
Bit 25: LCP Reset Button
Pressed
Bit 26: LCP Test Button
Pressed
Bit 27: Latch Active
Bit 28: Final Val Hi
Bit 29: Final Val Lo
Bit 0: Execution Failure
Bit 1: Write Lock Integrity
Bit 2: Mode Integrity
Bit 3: Event Queue
Exceeded
Bit 4: Sequence
Execution Error
AUTO
Bit 5: ISR Safety Monitor
MAN
82.3
Bit 18: PST Anomaly
OOS
Bit 19: FST Anomaly
Bit 21: PST Success
Bit 22: FST Success
Bit 23: PST Overdue
Bit 24: FST Overdue
Bit 25: PST Pending
Bit 30: Diagnostic in
Progress
83
Bit 0: Drive Current
Bit 1: Program Memory
Bit 2: Static Memory
Bit 3: Processor or I/O
AUTO
Processor
83.1
RW
MAN
Bit 4: Travel Sensor
OOS
Bit 5: Control Pressure
Sensor
Bit 6:Output Block
Timeout
Bits 7-31: (Reserved)
AUTO
Same as
MAN
SHUTDOWN_TRIGGER
83.2
RW
OOS
above.
Range
Initial Value
·LCP Comms
·Latch Active
·PST Anomaly
·FST Anomaly
·PST Success
·FST Success
·PST Pending
·Diagnostic in
Progress
All Bits: 0
All Bits: 0
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: Bit String
SETUP
0=disable
1=enable
Data Type: Bit String
0=disable
SETUP
1=enable
Data Type: Bit String
0=attempt control,
SETUP
1=fail to zero drive e.g. OOS mode
Action on specific instrument alerts.
Data Type: Bit String
0=Auto
1=Manual
SETUP
Recovery action after a shutdown
trigger "fail to zero drive" above.