D Calibration Location (XD_CAL_LOC [55]) indicates the location of the last instrument calibration .
D Calibration Date (XD_CAL_DATE [56]), enter a date with the format MM/DD/YY. Date is a user‐defined variable that
provides a place to save the date of the last calibration .
D Calibration Person (XD_CAL_WHO [57]) is th name of the person performing last calibration.

Valve and Actuator

Field Communicator
TB > Configure/Setup > Detailed Setup > Valve and Actuator
Valve
D Enter the identification number of the Valve Manufacturer (VALVE_MAN_ID [51]) on which the instrument is
mounted. Select from the drop‐down list or enter the manufacturer's identification number as defined by the
Fieldbus Foundation. For Fisher, the manufacturer ID hex value is 005100.
D Enter the Valve Model Number (VALVE_MODEL_NUM [52]), (design letter or type number) for the valve on which
the instrument is mounted.
D Enter the Valve Serial Number (VALVE_SN [53]) on which the instrument is mounted.
D Enter the Valve Style (VALVE_TYPE [54]), sliding‐stem or rotary, on which the instrument is mounted.
D Enter the Valve Size (VALVE_SIZE [100.1]) on which the instrument is mounted.
D Valve Class (VALVE_CLASS [100.2]) Enter the valve pressure class rating .
D Enter the valve Rated Travel (RATED_TRAVEL [26]) in inches or mm for sliding-stem valves, or in degrees of rotation
for rotary valves.
D Enter the Actual Travel (ACTUAL_TRAVEL [100.3]) in inches or mm for sliding-stem valves, or in degrees of rotation
for rotary valves.
D Enter the valve Shaft Stem Diameter (SHAFT_STEM_DIA [100.4]) in inches or millimeters.
D Enter the valve Packing Type (PACKING_TYPE [100.5).
D Enter the valve Inlet Pressure (INLET_PRESSURE [100.6]).
D Enter the valve Outlet Pressure (OUTLET_PRESSURE [100.7]) in psig, kPa, Bar, inHg, inH
Trim
D Enter the valve Seat Type (SEAT_TYPE [101.1]).
D Enter the valve Leak Class (LEAK_CLASS [101.2]).
D Enter the valve Port Diameter (PORT_DIAMETER [101.3]) in inches or mm.
D Enter the valve Port Type (PORT_TYPE [101.4]).
D Enter the Flow Direction (FLOWDIRECTION [101.5]) through the valve.
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
2
O, or kg/cm
.
2
February 2017