Fisher FIELDVUEDVC6200f Instruction Manual page 289

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
AI Function Block Parameter List
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shared Index Number indicates sub‐parameter
Table E‐26. Analog Input Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Process Value
PV
Primary Output
OUT
Simulate
SIMULATE
SIMULATE_STATUS
SIMULATE_VALUE
TRANSDUCER_STATUS
TRANSDUCER_VALUE
ENABLE/DISABLE
Transducer Scale
XD_SCALE
Index
RO /
Write Block
Number
RW
Mode
1
RO
N/A
2
ALL
3
ALL
4
ALL
5
5.1
RW
ALL
5.2
RO
ALL
5.3
RW
ALL
5.4
RW
ALL
6
RO
7
RO
8
OOS, MAN
9
9.1
ALL
9.2
ALL
9.3
RO
9.4
RO
9.5
ALL
10
OOS
Initial
Range
Value
0 to 65535
0
7 bit ASCII
spaces
0 to 65535
0
1 to 255
0
OOS until block
OOS
is configured,
MAN
then last valid
AUTO
target
OOS
OOS, MAN,
OOS+MAN+AUTO
AUTO
AUTO
1: Block Configuration
Error
3: Simulate Active
7: Input Failure/ Bad PV
Status
14: Power‐up
15: Out‐of‐Service
PV Status set equal to
FIELDV_VAL Status
OUT_STATE
0
0
0
0
0=Not Initialized
1=simulate
1=Simulation Disabled
disabled
2=Simulation Active
EU at 100%
100
EU at 10%
0
Units Index
%
Decimal Point
2
DVC6200f Digital Valve Controllers
AI Function Block
Description
Data Type: Unsigned16
The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed
Data Type: Octet String
The user description of the intended application of
the block.
Data Type: Unsigned16
The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
Data Type: DS‐69
Valid Bits: 7: OOS, 4: MAN, 3: AUTO
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: Bit String
0
Inactive
=
1
Active
=
Error status associated with the hardware or
software for the AI block.
Data Type: DS‐65
Reflects the scaled value from the configured
channel. Units set by OUT_SCALE and L_TYPE.
Data Type: DS‐68
The block output value and status.
Data Type: DS‐82
A group of data that contains the current transducer
value and status, the simulated transducer value
and status, and the enable/disable bit.
Data Type: DS‐68
Transducer scaling (XD_SCALE) is applied to the
value from the channel to produce the FIELD_VAL in
percent. The XD_SCALE units code must match the
channel units code (if one exists), or the block will
remain in OOS mode after being configured.
February 2017
289

Advertisement

Table of Contents
loading

Table of Contents